1 change-over to fixed setpoint, Change-over to fixed setpoint (c 274), 9400 highline | parameter setting & configuration – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual

Page 274

Advertising
background image

9400 HighLine | Parameter setting & configuration

Standard TAs

TA "Actuator – torque" | Speed limit value conditioning

274

Firmware 1.37 - 09/2006

L

11.3.5.1

Change-over to fixed setpoint

[11-18] Additional offset for the speed limit value (schematic diagram)

Via the digital input DI4 a change-over to a parameterisable fixed setpoint can take place.

r

Parameter setting: Tab Application parameter  Dialog level Overview

Use of further fixed setpoints
A total of 15 different fixed setpoints can be parameterised. For the selection of the fixed

setpoints 2 ... 15 the selection inputs are to be assigned with the corresponding signals.

The selection of the fixed setpoints is carried out in a binary coded manner.

r

Parameter setting: Tab Application parameter  Dialog level Overview  Ramp

generator  All fixed setpoints

Offset

Selection

LS_Torque...

M

Torque
setpoint

DI2

DI4

OUT

IN

Ramp generator

%

1

%

2

%

15

Fixed setpoints

Status

machine

(basic drive

functions)

Speed limit

AIN2

M

v

F

Parameters

Lenze setting

Value Unit

C03500/1

Fixed setpoint 1

10.00 %

Control inputs of the function

Signal configuration

Lenze setting

Control input

(Multiplexer parameters)

DigIn 4  Activate fixed setpoint 1

C03009/4

Parameters

Lenze setting

Value Unit

C03500/1

Fixed setpoint 1

10.00 %

C03500/2

Fixed setpoint 2

0.00 %

C03500/...

Fixed setpoint ...

... ...

C03500/15

Fixed setpoint 15

0.00 %

Control inputs of the function

Signal configuration

Lenze setting

Control input

(Multiplexer parameters)

DigIn 4  Activate fixed setpoint 1

C03009/4

FALSE  Activate fixed setpoint 2

C03009/5

FALSE  Activate fixed setpoint 4 a

C03009/6

FALSE  Activate fixed setpoint 8 a

C03009/7