9400 HighLine | Parameter setting & configuration

Diagnostics & error analysis

Error messages of the operating system

490

Firmware 1.37 - 09/2006

L

CAN on board RPDO1: Telegram not received or faulty [0x00870000]

CAN on board RPDO2: Telegram not received or faulty [0x00870001]

CAN on board RPDO3: Telegram not received or faulty [0x00870002]

CAN on board RPDO4: Telegram not received or faulty [0x00870003]

CAN on board PDO manager: Faulty configuration [0x00870008]

Response (Lenze setting printed in bold)

Setting:

C00591/1

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CAN on board: CAN-IN 1 error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has released.

• Set the correct telegram length for the CAN master

(transmitter).

• Remove electromagnetic interference (e.g. EMC).

• Select a different time monitoring or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C00591/2

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CAN on board: CAN-IN 2 error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has released.

• Set the correct telegram length for the CAN master

(transmitter).

• Remove electromagnetic interference (e.g. EMC).

• Select a different time monitoring or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C00591/3

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CAN on board: CAN-IN 3 error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has released.

• Set the correct telegram length for the CAN master

(transmitter).

• Remove electromagnetic interference (e.g. EMC).

• Select a different time monitoring or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C00591/4

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CAN on board: CAN-IN 4 error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has released.

• Set the correct telegram length for the CAN master

(transmitter).

• Remove electromagnetic interference (e.g. EMC).

• Select a different time monitoring or switch off time

monitoring.

Response (Lenze setting printed in bold)

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

CAN on board: CAN-PDO configuration error

• Faulty project download.

• Invalid CAN settings according to DS301V402 in the

Engineer or PLC Designer.

• Mapping variables have incorrect CANopen indices

according to DS405.

• Repeat download.

• Correct CAN settings in the project and regenerate

project.