9400 HighLine | Parameter setting & configuration

TAs for interconnection via electrical shaft

TA "Synchronism with mark synchronisation" | "Homing" mode

12.3.6

"Homing" mode

In the "Homing" mode (C03006 = "2") the drive is decoupled from the electrical shaft and

the basic function "Homing" is enabled:

[12-33] "Homing" mode (schematic diagram)

r

Parameter setting: Tab Application parameter  Dialog level Overview  Homing

v

t

LS_ManualJog

n

t

и

з

n

t

LS_Positioner

0

-100

100 200

LS_Homing

C03006 = 2

t

M

Slave

Parameters

Lenze setting

Value Unit

C02528

Traversing range

Modulo

C02640

Ref. mode

Set home pos. directly

C02642

HM position

0.0000 Unit

C02643

HM target position

0.0000 Unit

C02644

Ref. speed 1

360.0000 Unit/s

C02645

Home acceleration 1

720.0000 Unit/s

2

C02646

Ref. speed 2

180.0000 Unit/s

C02647

Ref. acceleration 2

360.0000 Unit/s

2

C02648

Home S-ramp time

100 ms

C02649

HM torque limit

10.00 %

C02650

Homing inhibit time

1.000 s

C02652

Home position after mains switching

Delete

C02653

Max. rot. angle after mains sw.

180 °

C3011

Set home position

Inactive

C3012

Home position

0.0000 Unit