1 setpoint inversion, 2 ramp generator, 1 setpoint inversion 11.3.4.2 ramp generator – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual

Page 272: 9400 highline | parameter setting & configuration

Advertising
background image

9400 HighLine | Parameter setting & configuration

Standard TAs

TA "Actuator – torque" | Torque setpoint conditioning

272

Firmware 1.37 - 09/2006

L

11.3.4.1

Setpoint inversion

[11-15] Setpoint inversion (schematic diagram)

Via the digital input DI3 the effective direction of the (bipolar) setpoint can be inverted, if

required.

r

Parameter setting: All parameters tab  Category Actuator - torque  Multiplexer

11.3.4.2

Ramp generator

[11-16] Ramp generator (schematic diagram)

In order to avoid setpoint step-changes the torque setpoint passes a ramp generator with

a parameterisable acceleration/deceleration and S-ramp time before it is transmitted to

the basic drive function "Torque follower".

r

Parameter setting: Tab Application parameter  Dialog level Overview

M

Gain

Invert setpoint

LS_Torque...

M

Torque
setpoint

DI2

DI3

OUT

IN

Ramp generator

Status

machine

(basic drive

functions)

Torque setpoint

AIN1

v

F

Control inputs of the function

Signal configuration

Lenze setting

Control input

(Multiplexer parameters)

DigIn 3  Invert setpoint

C03003

M

Gain

Invert setpoint

LS_Torque...

M

Torque
setpoint

DI2

DI3

OUT

IN

Ramp generator

Status

machine

(basic drive

functions)

Torque setpoint

AIN1

v

F

Parameters

Lenze setting

Value Unit

C03550

Acceleration / deceleration time

0.010 s

C03551

S-ramp time

0.001 s