9400 HighLine | Parameter setting & configuration

Motor interface

Extended commissioning | Optimise the response to setpoint changes by means of the torque

5.2.4

Optimise the response to setpoint changes by means of the torque feedforward control

Setting the load moment of inertia under

C00273/2

does not always provide the optimum

torque feedforward control. Depending on the application, an adaptation of the setting

under

C00273/2

may be necessary to optimise the response to position/speed control

setpoint changes.

[5-8]

Typical signal characteristics for different settings of the load moment of inertia

C00273/2

can be used to compensate for effects in addition to the moment of inertia

which are detected by the speed controller in the closed speed control loop (e.g. friction

torque).
Below you will find a description of a procedure for optimising the feedforward control

behaviour starting from the system's moment of inertia.

Without feedforward control:

C00273/2

set too low:

C00273/2

set too high:

Optimum feedforward control:

n

Speed setpoint (Speed.dnSpeedSetpoint signal)

o

Actual speed value (Speed.dnActualMotorSpeed signal)

p

Speed controller output (Torque.dnOutputSpeedCtrl signal)

q

Torque feedforward control (Torque.dnTotalTorqueAdd signal)