9400 HighLine | Parameter setting & configuration

Basic drive functions

Homing | Parameter setting

9.5.1.4

Homing to end stop
By selecting the homing modes 14 & 15, homing to end stop can be executed as follows:

1. The drive travels with reduced torque in positive direction (mode 14) or negative

direction (mode 15).

2. When the drives hits an end stop so that the torque limit set in

C02649

is exceeded for

the period of time defined in

C02650

, the reference is set.

– When a reference offset is set, it is traversed by this offset with correct sign.

9.5.1.5

Connection of reference switch
For the homing modes with reference switch, the control input HM_bHomingMark of the

system block

LS_Homing

must be connected to the digital input which is connected to the

reference switch.

9.5.1.6

Touch probe interface configuration
The touch probe channel to be used for homing with touch probe detection is selected in

the »Engineer« on the Application parameter tab in the overview  dialog level. All basic

functions  Homing  TP interface.

r

The setting carried out in this parameterisation dialog directly affects the setting of

C02651

("Ref. touch probe configuration") and vice versa.

r

For a direct setting of

C02651

(e.g. with keypad) the following table lists the decimal

values for all possible configurations.

r

Example: For selecting the touch probe channel "DIGIN 8" and response to only one

positive edge, it is required to set the decimal value "16384" in

C02651

.

Selection

Touch probe channel

Touch probe response
Positive edge

Negative edge

Both edges

DigIn 1

1

2

3

DigIn 2

4

8

12

DigIn 3

16

32

48

DigIn 4

64

128

192

DigIn 5

256

512

768

DigIn 6

1024

2048

3072

DigIn 7

4096

8192

12288

DigIn 8

16384

32768

49152

Motor encoder zero pulse

65536

Load encoder zero pulse

262144