9400 HighLine | Parameter setting & configuration

Diagnostics & error analysis

Error messages of the operating system

524

Firmware 1.37 - 09/2006

L

CAN module (MXI2): Faulty NMT slave configuration [0x00ad0021]

CAN module (MXI2): Faulty emergency configuration [0x00ae0000]

CAN module (MXI2): Node guarding error 1 [0x00af0000]

CAN module (MXI2): Node guarding error 2 [0x00af0001]

Response (Lenze setting printed in bold)

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

CANopen communication module in MXI2: A

configuration error has occurred in the network

management of the CAN slave.

• Faulty download of an Engineer or PLC Designer

project

• Invalid CAN settings according to DS301V402 in the

Engineer or PLC Designer.

• Incorrect parameterisation of node guarding or

heartbeat.

• Repeat download

• Correct CAN settings in the project and regenerate

project.

Response (Lenze setting printed in bold)

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

CANopen communication module in MXI2: In the CAN

emergency module a configuration error has occurred.

• Faulty download of an Engineer or PLC Designer

project

• Invalid CAN emergency settings according to

DS301V402 in the Engineer or PLC Designer.

• Repeat download

• Correct CAN settings in the project and regenerate

project.

Response (Lenze setting printed in bold)

Setting:

C14612/1

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CANopen communication module in MXI2: Cyclic node

monitoring

• CAN master has not received a response to a node

guarding telegram (remote transmission request

telegram) from node 1 within the defined time.

• Reactivate CAN node by restarting the controller,

restart of the controller (

C00002

="11000") or CAN

reset node.

• Select a different node guarding monitoring time or

switch off monitoring.

• Reset error state if latched.

Tip: Safe the current parameter set before mains

switching and restarting the controller (

C00002

="11").

Response (Lenze setting printed in bold)

Setting:

C14612/2

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CANopen communication module in MXI2: CAN master

has not received a response to a node guarding telegram

from node 2.

See remedy for "

Node guarding error 1

".