9400 HighLine | Parameter setting & configuration

Diagnostics & error analysis

Error messages of the operating system

Memory module: File system has been formatted [0x007c0000]

Memory module: File system has been restored [0x007c0001]

Analog input 1: Master current < 4 mA [0x007d0000]

Invalid PLC configuration [0x007d0001]

Communication error between device and device module [0x007f0002]

CAN on board: Bus-off [0x00830000]

Response (Lenze setting printed in bold)

…

None … System fault … Fault … Trouble … Quick stop by trouble … Warning locked … Warning : Information

Cause

Remedy

File system of the memory module has been formatted. - (Information only)

Response (Lenze setting printed in bold)

…

None … System fault … Fault … Trouble … Quick stop by trouble … Warning locked … Warning : Information

Cause

Remedy

File system of the memory module has been restored.

- (Information only)

Response (Lenze setting printed in bold)

Setting:

C00598

(; Adjustable response)

;

None … System fault : Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

Master current is in the impermissible range -4 ... +4 mA,

e.g. due to a line break or a defective master current

value encoder.

• Only for parameterisation as master current input

(see

C00034

).

Remove open circuit.

Response (Lenze setting printed in bold)

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

An invalid control configuration has occurred.

Load other application.

Response (Lenze setting printed in bold)

Setting:

C01501

(; Adjustable response)

:

None … System fault ; Fault … Trouble ; Quick stop by trouble ; Warning locked ; Warning … Information

Cause

Remedy

Communication between controller and extension

module is interrupted, e.g. due to disturbances in the

ambience (EMC), a defective hardware or loose contact.

• This monitoring is designed for safe process data

communication.

• Remove EMC fault.

• Properly connect module.

• Switch the mains or restart controller.

• Exchange module/controller.

• Please contact Lenze, if the problem occurs again.

Response (Lenze setting printed in bold)

Setting:

C00595

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CAN on board: "Bus-off" state

• Too many faulty telegrams received.

• Cable defective (e.g. loose contact).

• Two nodes with the same ID.

• Remove fault (e.g. EMC).

• Remove loose contact, screw down adapter.

• Assign different node IDs.