Memory module is defective or missing [0x00680002, Safety module is defective or missing [0x00680003, Mxi1: module changed during operation [0x00680004 – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual

Page 450: Mxi2: module changed during operation [0x00680005, Memory module has been removed [0x00680006, 9400 highline | parameter setting & configuration

Advertising
background image

9400 HighLine | Parameter setting & configuration

Diagnostics & error analysis

Error messages of the operating system

450

Firmware 1.37 - 09/2006

L

Memory module is defective or missing [0x00680002]

Safety module is defective or missing [0x00680003]

MXI1: Module changed during operation [0x00680004]

MXI2: Module changed during operation [0x00680005]

Memory module has been removed [0x00680006]

Response (Lenze setting printed in bold)

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Operating system could not identify the memory

module.

Mains switching

• If the error occurs again: Switch off the controller,

remove memory module and plug in again, switch on

the controller again.

• If the error still occurs: Switch off controller and use a

different memory module.

Response (Lenze setting printed in bold)

…

None : System fault … Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Operating system could not identify the safety module. Mains switching

• If the error occurs again: Switch off the controller,

remove safety module and plug in again, switch on

the controller again.

• If the error still occurs: Switch off controller and use a

different safety module.

Response (Lenze setting printed in bold)

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

The extension module you have tried to plug into the

module receptacle MXI1 is not "hot plug" capable.

Plug in valid module and restart controller.

• Through mains switching, the system accepts

modules without "hot plug" capability in the

following switch-on phase.

Response (Lenze setting printed in bold)

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

The extension module you have tried to plug into the

module receptacle MXI2 is not "hot plug" capable.

Plug in valid module and restart controller.

• Through mains switching, the system accepts

modules without "hot plug" capability in the

following switch-on phase.

Response (Lenze setting printed in bold)

…

None : System fault … Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

You have tried to remove or change the memory module

during operation.

Switch off the controller, plug in memory module and

switch on the controller again.

• If the error occurs again, the memory module is

defective and must be replaced.