Application has been stopped [0x006a0014, 9400 highline | parameter setting & configuration – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual

Page 461

Advertising
background image

L

Firmware 1.37 - 09/2006

461

9400 HighLine | Parameter setting & configuration

Diagnostics & error analysis

Error messages of the operating system

Application has been stopped [0x006a0014]

PDO mapping (MXI1): Faulty configuration [0x006a0015]

PDO mapping (MXI2): Faulty configuration [0x006a0016]

Control card: Supply voltage (24 V DC) too low [0x006f0000]

Response (Lenze setting printed in bold)

…

None … System fault … Fault … Trouble … Quick stop by trouble … Warning locked … Warning : Information

Cause

Remedy

The application in the controller has been stopped.

- (Information only)

Response (Lenze setting printed in bold)

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

CANopen communication module in MXI1: Incorrectly

configured process data mapping.

• The corresponding PDO channel is not installed, since,

for instance, no communication module has been

selected for the module receptacle MXI1 in the

Engineer project.

• The communication module selected for the module

receptacle MXI1 in the Engineer project does not

support PDO mapping.

• The mapping information downloaded to the

controller is faulty.

• Integrate suitable communication module into the

Engineer project for the module receptacle MXI1.

• Check the configuration of the network. Then

recompile the project and transmit it to the controller.

Response (Lenze setting printed in bold)

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

CANopen communication module in MXI2: Incorrectly

configured process data mapping.

• The corresponding PDO channel is not installed, since,

for instance, no communication module has been

selected for the module receptacle MXI2 in the

Engineer project.

• The communication module selected for the module

receptacle MXI2 in the Engineer project does not

support PDO mapping.

• The mapping information downloaded to the

controller is faulty.

• Integrate suitable communication module into the

Engineer project for the module receptacle MXI2.

• Check the configuration of the network. Then

recompile the project and transmit it to the controller.

Response (Lenze setting printed in bold)

…

None … System fault … Fault : Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

External supply voltage UB24 of the control card is lower

than 18 V.

Check external supply voltage.

• If the external supply voltage is available and the

error message does not disappear, please contact

Lenze.