9400 HighLine | Parameter setting & configuration

Basic drive functions

Homing | Executing homing

9.5.2.1

Setting reference search/setting reference directly
By setting the control input HM_bActivateHoming to TRUE, the reference search in the

selected homing mode is started.

r

During reference search, the status output HM_bActive is set to TRUE.

r

When the reference search is completed, the status output HM_bActive is reset to

FALSE and the status output HM_bDone is set to TRUE.

r

When the home position could be detected, the status output HM_bHomePosAvailable

is set to TRUE.

9.5.2.2

Loading home position via input
By setting the control input HM_bLoadHomePos to TRUE the "tool position" applied to

input HM_dnHomePos_p is accepted manually as home position with drive at standstill.

9.5.2.3

Resetting home position
By setting the control input HM_bResetHomePos to TRUE the status "Reference known" is

reset.

r

The status outputs HM_bDone and HM_bHomePosAvailable are reset to FALSE.

Note!

In the homing mode "100: Set reference directly" no reference search will be

started but the home position set in

C02642

will be directly accepted.