9400 HighLine | Parameter setting & configuration

Parameter reference

Parameter list | C00173

560

Firmware 1.37 - 09/2006

L

C00173

C00174

C00175

C00176

Parameter | Name:

C00173 | Mains voltage

Data type: UNSIGNED_8

Index: 24402

d

= 5F52

h

Adaptation of the DC bus voltage thresholds

• Check during commissioning and adapt, if necessary.

• All drive components in DC bus connections must have the same thresholds.

• LU = Undervoltage threshold, OU = Overvoltage threshold

Note:Altering this setting also has an impact on the permissible device utilisation!

In the chapter "Rated data" of the Hardware Manual the corresponding permissible device utilisation for the

different device types at a certain mains voltage and switching frequency is specified.
Selection list

(Lenze setting printed in bold)

Information

0 230 V, LU = 150 V

Operation on 230 V mains

• LU = 150 V, OU = 400 V

• Brake chopper threshold = 390 V

1 400/415 V, LU = 285 V

Operation on 400 V mains/415 V mains

• LU = 285 V, OU = 800 V

• Brake chopper threshold = 725 V

2 460/480 V, LU = 328 V

Operation on 460 V mains/480 V mains

• LU = 328 V, OU = 800 V

• Brake chopper threshold = 765 V

3 500 V, LU = 342 V

Operation on 500 V mains

• LU = 342 V, OU = 800 V

• Brake chopper threshold = 790 V

4 230 V, LU configurable

Operation on 230 V mains

• LU is selected under

C00174

• OU = 400 V

• Brake chopper threshold = 390 V

5 400/415 V, LU configurable

Operation on 400 V mains/415 V mains

• LU is selected under

C00174

• OU = 800 V

• Brake chopper threshold = 725 V

6 460/480 V, LU configurable

Operation on 460 V mains/480 V mains

• LU is selected under

C00174

• OU = 800 V

• Brake chopper threshold = 765 V

7 500 V, LU configurable

Operation on 500 V mains

• LU is selected under

C00174

• OU = 800 V

• Brake chopper threshold = 790 V

;

Read access ; Write access … CINH … PLC STOP … No transfer … COM … MOT

Parameter | Name:

C00174 | Threshold - undervoltage (LU)

Data type: UNSIGNED_32

Index: 24401

d

= 5F51

h

With

C00173

= 4 ... 7 the LU threshold can be freely selected

Setting range

(min. value | unit | max. value)

Lenze setting

15

V

342 285 V

;

Read access ; Write access … CINH … PLC STOP … No transfer … COM … MOT

Parameter | Name:

C00175 | Service code

Data type: UNSIGNED_32

Index: 24400

d

= 5F50

h

This code is used internally by the controller and must not be overwritten by the user!

Parameter | Name:

C00176 | Service code

Data type: UNSIGNED_32

Index: 24399

d

= 5F4F

h

This code is used internally by the controller and must not be overwritten by the user!