2 drive diagnostics via keypad/bus system, 9400 highline | parameter setting & configuration – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual

Page 434

Advertising
background image

9400 HighLine | Parameter setting & configuration

Diagnostics & error analysis

Drive diagnostics via keypad/bus system

434

Firmware 1.37 - 09/2006

L

15.2

Drive diagnostics via keypad/bus system

Keypad display of the controller state

Display parameters
Via the parameters listed in the following tables current states and actual values of the

controller can be queried for diagnostic purposes, e.g. by using the keypad, a bus system or

the »Engineer« (with an online connection to the controller).

r

These parameters are listed in the »Engineer« parameter list and the keypad in the

Diagnostics category.

r

For a detailed parameter description, please see the chapter "

Parameter reference

".

(C 537)

r

When the keypad at the front of the controller is

connected to the diagnostic interface X6, the status of

the controller is displayed via different symbols on the

LDC display in the area n.

Icon

Meaning

Note

b

Controller is ready for operation.

f

Controller is enabled.

g

Application in the controller is stopped.

h

Quick stop is active

i

Controller is inhibited.

The power outputs are inhibited.

`

Controller is ready to start.

j

Speed controller 1 in the limitation.

The drive is torque-controlled.

k

Set current limit has been exceeded in motor

or generator mode.

l

Pulse inhibit is active

The power outputs are inhibited.

Z

System fault is active

Y

Fault is active

[

Trouble is active

\

Quick stop by trouble is active

]

Warning is active

Parameters

Display

C00183

Device state

C00168

Error number

C00051

Actual speed

C00052

Motor voltage