Initial commissioning | Optimise the switching performance of the inverter

5.1.7

Optimise the switching performance of the inverter

An inverter generates a pulse-width-modulated, three-phase voltage system. Due to the

design of the inverter, current-dependent and chopper-frequency-dependent losses inside

of the inverter falsify the output voltage. Since the output voltage is not measured, the

losses must be compensated by a suitable feedforward control. This is compensated via an

inverter error characteristic.
The inverter error characteristic depends, among other things, on the motor cable length

and for a motor with unknown motor parameters it must be detected at least once

individually with the device command "Detect inverter characteristic" so that a sinusoidal

current is ensured for an automatic selection of the motor parameters.

M

How to determine the inverter error characteristic:

1. If the controller is enabled, inhibit the controller, e.g. with the device command

"Inhibit controller" (

C00002

= "41").

2. Execute the device command "Determine inverter characteristic" with

C00002

= "71".

The procedure starts with controller enable, if
• no other identification is active,
• no error (TRIP) has occurred, and
• no test mode is activated.
If one of the above conditions is not met, the procedure is cancelled and the

corresponding controller command status is indicated under

C00003

.

Note:

By means of controller inhibit the started procedure can be aborted any time.

Characteristic values already detected are not considered.
For detailed information about the procedure, please see the following section

"Sequence".

O

Tip!
For controller enable all sources for controller inhibit must be reset. In

C00158

the

sources for controller inhibit are displayed in a bit-coded manner.
The status of the controller command activated under

C00002

is indicated under

C00003

.

Note!

Not required if a Lenze motor is operated on the controller!
For an external motor with unknown motor parameters the optimisation of the

inverter switching performance is necessary for the motor parameter setting

described in the following chapter.

Set motor parameters

(C 75)