9400 highline | parameter setting & configuration – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual

Page 530

Advertising
background image

9400 HighLine | Parameter setting & configuration

Diagnostics & error analysis

Error messages of the operating system

530

Firmware 1.37 - 09/2006

L

CAN module (MXI2): Faulty NMT master configuration [0x00af0020]

CAN module (MXI2) RPDO1: Telegram not received or faulty [0x00b00000]

CAN module (MXI2) RPDO2: Telegram not received or faulty [0x00b00001]

CAN module (MXI2) RPDO3: Telegram not received or faulty [0x00b00002]

Response (Lenze setting printed in bold)

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

CANopen communication module in MXI2: A

configuration error has occurred in the network

management of the CAN master.

• Faulty download of an Engineer or PLC Designer

project.

• Invalid CAN master settings according to DS301V402

and DS405 in the Engineer or PLC Designer.

• Incorrect parameterisation of node guarding or

heartbeat.

• Repeat download

• Correct CAN settings in the project and regenerate

project.

Response (Lenze setting printed in bold)

Setting:

C14591/1

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CANopen communication module in MXI2: CAN-IN 1

error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has released.

• Set the correct telegram length for the CAN master

(transmitter).

• Remove electromagnetic interference (e.g. EMC).

• Select a different time monitoring or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C14591/2

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CANopen communication module in MXI2: CAN-IN 2

error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has released.

• Set the correct telegram length for the CAN master

(transmitter).

• Remove electromagnetic interference (e.g. EMC).

• Select a different time monitoring or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C14591/3

(; Adjustable response)

:

None … System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information

Cause

Remedy

CANopen communication module in MXI2: CAN-IN 3

error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has released.

• Set the correct telegram length for the CAN master

(transmitter).

• Remove electromagnetic interference (e.g. EMC).

• Select a different time monitoring or switch off time

monitoring.