Cpu: overtemperature [0x00770009, Heatsink: temperature sensor defective [0x0077000a, Motor: temperature sensor defective [0x0077000c – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual

Page 465: 9400 highline | parameter setting & configuration

Advertising
background image

L

Firmware 1.37 - 09/2006

465

9400 HighLine | Parameter setting & configuration

Diagnostics & error analysis

Error messages of the operating system

CPU: Overtemperature [0x00770009]

Heatsink: Temperature sensor defective [0x0077000a]

Inside the device: Temperature sensor defective [0x0077000b]

Motor: Temperature sensor defective [0x0077000c]

DC-bus capacitor: Temperature sensor defective [0x0077000d]

Response (Lenze setting printed in bold)

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

CPU temperature higher than fixed limit temperature

(85 °C).

• Controller ambient temperature too high.

• Dirty fan or ventilation slots.

• Check control cabinet temperature.

• Clean filter.

• Clean controller.

Response (Lenze setting printed in bold)

Setting:

C00588

(; Adjustable response)

;

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked ; Warning … Information

Cause

Remedy

Encoder for heatsink temperature supplies undefined

values.

Check control cabinet temperature, maybe it is too low.

Response (Lenze setting printed in bold)

Setting:

C00588

(; Adjustable response)

;

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked ; Warning … Information

Cause

Remedy

Encoder for interior temperature supplies undefined

values.

Check control cabinet temperature, maybe it is too low.

Response (Lenze setting printed in bold)

Setting:

C00594

(; Adjustable response)

;

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked ; Warning … Information

Cause

Remedy

The signals of the connected encoder of the motor

temperature detection (resolver at X7 or encoder at X8)

are outside the defined operating range of detection.

• Check bonding of the encoder cable at the motor and

controller.

• Check selection of the motor temperature sensor in

C01190

and make sure that it complies with the

assembly in the motor.

• Possibly switch off temperature sensor monitoring

(

C00594

="0").

• If a PTC is in the motor, activate the monitoring of the

PTC temperature in

C00585

instead.

Response (Lenze setting printed in bold)

Setting:

C00588

(; Adjustable response)

;

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked ; Warning … Information

Cause

Remedy

Encoder for capacitor temperature supplies undefined

values.

Check control cabinet temperature, maybe it is too low.