10 quick stop, 9400 highline | parameter setting & configuration – Lenze E94AxHE Servo Drives 9400 HighLine (Firmware 01-37) User Manual

Page 319

Advertising
background image

L

Firmware 1.37 - 09/2006

319

9400 HighLine | Parameter setting & configuration

TAs for interconnection via electrical shaft

TA "Electronic gearbox" | Quick stop

12.2.10

Quick stop

[12-20] Basic function "Quick stop" (schematic diagram)

r

The quick stop function can be activated as follows in the Lenze setting:
– By setting the digital input DI1 to LOW level.
– By a master control via the port LPortControl1:

By setting bit 2 of the bit-coded control word 1.

r

Parameter setting: Tab Application parameter  Dialog level Overview  All basic

functions  Quick stop

O

Tip!
Detailed information on quick stop can be found in chapter "Basic drive functions"



subchapter "

Quick stop

".

(C 152)

The basic function "Quick stop" brakes the

drive to standstill within the deceleration

time set for the quick stop function after a

corresponding request independent of the

setpoint selection.
If the quick stop function is deactivated,

the drive is led to the selected setpoint

again via the set acceleration time.

v

t

t

M

Slave

n

t

LS_Limiter

n

t

LS_Quickstop

STOP

Parameters

Lenze setting

Value Unit

C00105

Quick stop deceleration time

0.000 s

C00106

Quick stop S-ramp time

0.00 %

C00107

Reference for deceleration time "Quick stop"

Motor reference speed (

C00011

)

Control inputs of the function

Signal configuration

Lenze setting

Control input

(Multiplexer parameters)

DigIn 1  Activate quick stop 1

C03135/1

Control word 1

bit 02



Activate quick stop 2

C03135/2

FALSE  Activate quick stop 3

C03135/3