Initial commissioning | Optimise current controller

5.1.11

Optimise current controller

In a test mode you can select current setpoint step-changes and optimise the parameter

settings of the current controller (gain and reset time).

M

How to optimise the current controller in the test mode:

1. If the controller is enabled, inhibit the controller, e.g. with the device command

"Inhibit controller" (

C00002

= "41").

2. Activate the test mode for the current controller with

C00398

= "2".

3. Select the effective value of the current setpoint step change under

C00022

.

• The peak value of the measurable motor current will be 1.41 times higher.

4. Enable the controller for a short time and measure the step response of the motor

current in the motor phases using the oscilloscope and clamp-on ammeters or

record the field-oriented direct-axis current using the

Oscilloscope

function in the

»Engineer«.

(C 416)

• Motor control variable to be recorded:

current.dnDirectCurrentAct (field-oriented direct-axis current)

5. Evaluate the step response:

6. Change the gain Vp under

C00075

and the reset time Tn under

C00076

.

7. Repeat steps 4 ... 6 until the optimum step response of the motor brake is reached.

• After optimisation, the current control time is typically 0.5 ... 1 ms.
• If the adjustment results are not satisfactory, the decoupling network can be

additionally activated via the setting

C00074

= "1". After this, repeat the steps

2 ... 6.

• In case of MCS results may only be achieved with a current-dependent

correction of the leakage inductance. For this purpose, it is required to use a

motor with an electronic nameplate (ENP) or to set the saturation characteristic

manually (see the following section).

I

t

I

t

I

t

I

t

I

t

I

t

I

t

I

t

I

t

Vp < Vp opt.

Vp = Vp opt.

Vp > Vp opt.

Tn

<

Tn

opt.

Tn

=

Tn

opt.

Tn

>

Tn

opt.