9400 HighLine | Parameter setting & configuration

TAs for positioning tasks

TA "Multi-purpose positioning" | Program flow

380

Firmware 1.37 - 09/2006

L

Variable branching

For variable branches (jumps) 5 actions of type "Variable branching" are available.

• The branch to one of 20 possible steps is executed depending on the value in C03001 ... C03005

at the time or processing.

• The parameters C03001 ... C03005 are firmly assigned to the five available actions:

–C03001 determines the branch for action 1.

–C03002 determines the branch for action 2, etc.

Example:

If C03002 is assigned to the value "15" at the time of processing the action no. 2, it is branched to

the step which is entered in the parameter "Sequence step at branch value 15" for action no. 2

(C04554/2).
Parameters

Information

C04540/1...5

Sequence step at

branch value 1

Step which is executed next when C03001 ... C03005 = "1".

• With the default setting "0" the branching is deactivated

(sequence step is processed).

C04541/1...5

Sequence step at

branch value 2

Step which is executed next when C03001 ... C03005 = "2".

• In the default setting "0", branching is deactivated and

the next step in the sequence table is processed.

...

...

...

C04559/1...5

Sequence step at

branch value 20

Step which is executed next when C03001 ... C03005 = "20".

• In the default setting "0", branching is deactivated and

the next step in the sequence table is processed.

Switching

In order to switch digital output signals 25 actions of type "Switching" are available.

• Each action can set two selectable sequencer outputs to FALSE or TRUE independently of each

other.

Sequencer outputs (C 386)

Parameters

Information

C04520/1...25

Output A

switching

Sequencer output 1 ... 32 to be switched.

• With the setting "0" switching is deactivated.

C04521/1...25

Signal state for A

switching

State to which the sequencer output is to be set.

C04522/1...25

Output for B

switching

Sequencer output 1 ... 32 to be switched.

• With the setting "0" switching is deactivated.

C04523/1...25

Signal state for B

switching

State to which the sequencer output is to be set.

Set counter

10 actions of type "Set counter" are available for setting one of the 10 available counters to a certain

starting value.

• The 10 actions of type "Set counter" are not firmly assigned to the 10 actions of the "Counting"

type.

• You can use, for instance, an action of type "Set counter" to set a counter to a value and later you

can set the same counter with another action of type "Set counter" to another value.

Parameters

Information

C04580/1...10

Counter selection With the setting "0" the setting of the counter is deactivated.

C04581/1...10

New counter

content

-2147483648 ... 2147483648

C04582/1...10

Current counter

content

Read only

Action type

Function/parameter

1

n

2

0

Set

0 0