9400 HighLine | Parameter setting & configuration

Basic drive functions

Brake control | Parameter setting

Further torque feedforward control options

[9-17] Feedforward control with parameterised starting torque

Application example:
The load for a hoist drive is always known. For an optimum behaviour a torque

proportional to the load and 10 Nm in addition as constant precontrol value are to be

loaded in the speed controller.

r

The starting torque 1 is used as constant precontrol value (

C02586

="10 Nm",

C02588

= "0" and BRK_bStartingTorque2 = FALSE).

r

Via the input BRK_dnTorqueAdd_n the torque is specified proportional to the load.

r

An additional precontrol value can be

set via the input BRK_dnTorqueAdd_n.

1

0

BRK_dnTorqueAdd_n

CTRL

Speed controller