9400 HighLine | Parameter setting & configuration

Basic drive functions

Brake control | Mode 2/12: Automatic control of the brake

224

Firmware 1.37 - 09/2006

L

9.11.4.1

Behaviour at pulse inhibit
In case of pulse inhibit the brake is applied. This occurs according to the parameter setting

in

C02582

either immediately (default setting) or delayed when the threshold set for brake

activation is fallen below, which can be selected to protect the brake if high centrifugal

masses occur.

Activate the brake in any case
When setting

C02582

= "0", the brake is triggered to close to prevent the mechanics from

being damaged.

Only activate the brake below the threshold set for brake activation
When

C02582

= "1", the brake remains released until the threshold set in

C02581

for brake

activation has been reached to protect the brake from excessive wear.

r

Braking is exclusively executed by the friction of the load mechanics.

r

Only when the motor speed has reached the threshold for brake activation, the brake

will be closed.

Note!

Pulse inhibit can be set in the enabled controller e.g. due to a DC overvoltage

during brake operation by a wrong dimensioning of the brake resistor.



Stop!

Do not set the threshold for brake activation in

C02581

too high to protect the

brake from wear.