TAs for positioning tasks

TA "Multi-purpose positioning" | Program flow

Count

25 actions of type "Count" are available for counting processes.

• With each action processing the counter content of the counter selected is increased or reduced

by the specified step value depending on the setting (count upwards or downwards).

• When the comparison condition for comparing the counter content with an adjustable

comparison value is fulfilled, a branch to any step is possible.

• 10 actions of type "Set counter" are available for setting a counter to a starting value.
Parameters

Information

C04590/1...25

Counter selection With the setting "0" the setting of the counter is deactivated.

C04591/1...25

Step value

Value by which the counter is increased or reduced.

• Range: -2147483648 ... 2147483648

C04592/1...25

Comparison

value

Value with which the counter is compared.

• Range: -2147483648 ... 2147483648

C04593/1...25

Sequence step

When the set comparison condition is met, a branch to the

step set here is executed.

If the condition is not met, the next step in the sequence

table is processed instead.

C04594/1...25

Comparison

condition

Selection of the condition for the comparison of the counter

content with the comparison value.

Wait

25 actions of type "Wait" are available for the insertion into the program flow.

• The sequence step is only processed after the waiting time has elapsed or when the selected

sequencer input has the selected signal state at the time of processing.

Sequencer inputs

(C 386)

Parameters

Information

C04571/1...25

Waiting time

With setting "0", the waiting time is deactivated.

C04572/1...25

Input for waiting

function

Sequence input 1 ... 32 to be evaluated.

• The sequence step will be processed when this input has

the set state, but no later than after the set waiting time

has elapsed.

C04573/1...25

Signal state for

waiting function

Required state for completing the waiting function.

Stand-by

5 actions of type "Stand-by" are available for the temporary activation of a setpoint follower.

• For a sensible use of the "Standby" action, appropriate signal combinations are required in the

(enabled) function block editor.

• The setpoint follower is enabled until the condition for exiting the stand-by is met.
Parameters

Information

C04601/1...5

Input for "Stand-

by" end

Sequence input 1 ... 32 to be evaluated.

C04602/1...5

Signal state for

"Stand-by" end

Only if the sequencer input to be evaluated has this state,

the standby step is exited, and the next step in the sequence

table is processed.

Program end

To define the program end in the sequence table or delete a program step, the action of type

"Program end" is available.

Action type

Function/parameter

1

3
4

2

Standby

End