9400 HighLine | Parameter setting & configuration

I/O terminals

Digital inputs

7.4

Digital inputs

The controller has 8 freely configurable digital inputs.

r

All digital inputs can be used for touch probe.

Touch probe detection

(C 129)

r

Control input RFR of terminal strip X5 for controller enable is connected to the device

control.

7.4.1

Terminal assignment/electrical data

7.4.2

Parameter setting

Short overview of parameters for the digital inputs:

Terminal

Use

Electrical data

X5/DI1

X5/DI8

Digital inputs 1 ... 8

LOW level: 0 ... +5 V

HIGH level: +15 ... +30 V

Input current: 8 mA per input

(at 24 V)

Electric strength of

external voltage:

max. ±30 V

Conversion rate: 1 kHz

X5/RFR

Controller enable

See digital inputs

X5/GI

Reference potential (digital ground)

X5

GI

RFR

DI1

DI2

DI3

DI4

DI5

DI6

DI7

DI8

Parameter

Information

C00114

DIx terminal polarity

C00443

DIx status

C02803

Status word dig. inputs

C02830

DIx delay time

Highlighted in grey = display parameter