9400 HighLine | Parameter setting & configuration

Motor interface

Initial commissioning | Set motor parameters

76

Firmware 1.37 - 09/2006

L

M

How to determine the motor parameters:

1. If the controller is enabled, inhibit the controller, e.g. with the device command

"Inhibit controller" (

C00002

= "41").

2. Execute the controller command "Determine motor parameters" with

C00002

= "72".

The procedure starts with controller enable, if
• no other identification is active,
• no error has occurred, and
• no test mode is activated.
If one of the above conditions is not met, the procedure is cancelled and the

corresponding controller command status is indicated under

C00003

.

Note:

By means of controller inhibit the started procedure can be aborted any time

without changing the codes for the motor parameters.
For detailed information about the procedure, please see the following section

"Sequence".

O

Tip!
For controller enable all sources for controller inhibit must be reset. In

C00158

the

sources for controller inhibit are displayed in a bit-coded manner.
The status of the controller command activated under

C00002

is indicated under

C00003

.