9400 HighLine | Parameter setting & configuration

Motor interface

Parameter setting | Motor monitoring (I²xt)

Structure of the I2xt monitoring
The introduction of a two-component model with two time constants (one for the winding

and the other for the housing/steel plates) serves to display the thermal behaviour of the

motor up to 500% of the rated current:

[5-11] Structure of the motor monitoring

Executing the calculation with only one time constant
With the setting

C01195

= "0 %" the time constant for the winding is not considered and

the thermal model is only calculated with the time constant set for the housing/steel

plates.

r

The setting

C01195

= "0 %" is e.g. sensible if not both time constants are known.

r

The calculation simplified due to this setting corresponds to the calculation in the

previous Lenze devices (e.g. servo inverter 9300 or ECS).

n

Thermal utilisation of the motor in [%]

k

1

1

(1 + p

)

t

1

k

2

1

(1 + p

)

t

2

I

act Motor

I

perm Motor

(n)

2

Œ

Parameters

Setting

I

act motor

Current motor current

-

I

perm motor

(n)

Permissible motor current (speed-dependent)

-

τ

1

Therm. time constant coil

C00128/1

k

1

Percentage of the winding in the final temperature

C01195

τ

2

Therm. time constant plates

C00128/2

k

2

Percentage of the steel plates in the final temperature

100 % -

C01195